Natatorium Building Enclosure Deterioration Due to Moisture Migration

ADD TO MY LIST
 
Author(s): Lawrence Graham | Mark Scott | Aleka Pappas

Journal: Buildings
ISSN 2075-5309

Volume: 2;
Issue: 4;
Start page: 534;
Date: 2012;
Original page

Keywords: CMU deterioration | fa&#231 | ade deterioration | natatorium design | humidity control | HVAC pressurization | natatorium pressurization | recreation center

ABSTRACT
The natatorium enclosure at the Avon Recreation Center in Avon, Colorado experienced significant deterioration of the CMU façade due to moisture carried by humid air from the interior of the space into the wall assembly. This situation was caused by a combination of an insufficient interior air and vapor barrier along with an HVAC system that failed to provide negative pressurization to the space. This case study describes the investigation carried out to determine the causes of wall and roof deterioration at the building, and details the repair efforts undertaken. Lessons learned are presented to help designers, building owners, and maintenance personnel prevent similar problems from occurring in their buildings.